HYDROSTATION
Hydrostation is the new IE5 efficiency class electronic system for constant pressure…
AISI 304 stainless steel in-line centrifugal pump, with suction and discharge on the same axis, equipped with high-efficiency ventilated motor. Suitable for circulation, civil and industrial heating systems. Read more
Flow rate | from 1.2 to 12 m³/h |
Total head | from 2.4 to 12.5 m |
Max. working pressure | 2 bar for LPS single-phase and LPS 25 three-phase 4 bar for LPS 32 three-phase |
Max. temperature of the liquid | -10°C ÷ +100°C |
MEI | > 0.4 |
Poles | 2 |
Insulation class | F |
Protection degree | IP55 |
Voltage | Single-phase 1~230V ±10% Three-phase 3~230/400V ±10% |
Pump body | AISI 304 (EN 1.4301) |
Impeller | AISI 304 (EN 1.4301) |
Shaft | Stainless steel AISI 303 (EN 1.4305) (part in contact with liquid) |
Mechanical seal | Ceramic/Carbon/NBRH |
Motor support | Aluminium |
What is the circulator's supply voltage?
The circulator’s supply voltage is 230V
What is the correct position and installation for circulators and in-line pumps?
Please check the pictograms in the instruction manual.
What wattage can be used for star connections?
Above 7.5 kW, we suggest to use this kind of start-up in order to limit very high inrush currents.
What percentage of glycol can be used in the system when the circulator is used for cooling?
The maximum amount of glycol that can be used is 20%.
How do I check the in-line pump's direction of rotation?
The in-line pump’s direction of rotation has to be checked every time a new installation is carried out.
We suggest to follow the steps given below:
The correct direction of rotation is clockwise.
If it’s not, reverse the phases of the pump’s motor.
Can I change the circulator’s settings?
If the circulator has a display, its functions can be changed according to the system’s requirements.
Contact us